<?xml version="1.0" encoding="utf-8" standalone="no"?>
<dublin_core schema="dc">
<dcvalue element="contributor" qualifier="author">Jung,&#x20;D</dcvalue>
<dcvalue element="contributor" qualifier="author">Lee,&#x20;Y</dcvalue>
<dcvalue element="contributor" qualifier="author">Park,&#x20;B</dcvalue>
<dcvalue element="contributor" qualifier="author">Kang,&#x20;B</dcvalue>
<dcvalue element="date" qualifier="accessioned">2024-01-21T13:12:29Z</dcvalue>
<dcvalue element="date" qualifier="available">2024-01-21T13:12:29Z</dcvalue>
<dcvalue element="date" qualifier="created">2022-01-10</dcvalue>
<dcvalue element="date" qualifier="issued">2000-11</dcvalue>
<dcvalue element="identifier" qualifier="issn">0140-7007</dcvalue>
<dcvalue element="identifier" qualifier="uri">https:&#x2F;&#x2F;pubs.kist.re.kr&#x2F;handle&#x2F;201004&#x2F;140967</dcvalue>
<dcvalue element="description" qualifier="abstract">In&#x20;this&#x20;study,&#x20;computer&#x20;simulation&#x20;programs&#x20;were&#x20;developed&#x20;for&#x20;multi-stage&#x20;condensation&#x20;heat&#x20;pumps&#x20;and&#x20;their&#x20;performance&#x20;was&#x20;examined&#x20;for&#x20;CFC11,&#x20;HCFC123,&#x20;HCFC141b&#x20;under&#x20;the&#x20;same&#x20;condition.&#x20;The&#x20;results&#x20;showed&#x20;that&#x20;the&#x20;coefficient&#x20;of&#x20;performance&#x20;(COP)&#x20;of&#x20;an&#x20;optimized&#x20;&amp;apos;non-split&#x20;type&amp;apos;&#x20;three-stage&#x20;condensation&#x20;heat&#x20;pump&#x20;was&#x20;25-42%&#x20;higher&#x20;than&#x20;that&#x20;of&#x20;a&#x20;conventional&#x20;single-stage&#x20;heat&#x20;pump.&#x20;The&#x20;increase&#x20;in&#x20;COP&#x20;differed&#x20;among&#x20;the&#x20;fluids&#x20;examined.&#x20;The&#x20;improvement&#x20;in&#x20;COP&#x20;was&#x20;due&#x20;largely&#x20;to&#x20;the&#x20;decrease&#x20;in&#x20;average&#x20;temperature&#x20;difference&#x20;between&#x20;the&#x20;refrigerant&#x20;and&#x20;water&#x20;in&#x20;the&#x20;condensers,&#x20;which&#x20;resulted&#x20;in&#x20;a&#x20;decrease&#x20;in&#x20;thermodynamic&#x20;irreversibility.&#x20;For&#x20;the&#x20;three-stage&#x20;heat&#x20;pump,&#x20;the&#x20;highest&#x20;COP&#x20;was&#x20;achieved&#x20;when&#x20;the&#x20;total&#x20;condenser&#x20;area&#x20;was&#x20;evenly&#x20;distributed&#x20;to&#x20;the&#x20;three&#x20;condensers.&#x20;For&#x20;the&#x20;two-stage&#x20;heat&#x20;pump,&#x20;however,&#x20;the&#x20;optimum&#x20;distribution&#x20;of&#x20;total&#x20;condenser&#x20;area&#x20;varied&#x20;with&#x20;working&#x20;fluids.&#x20;For&#x20;the&#x20;three-stage&#x20;system,&#x20;splitting&#x20;the&#x20;condenser&#x20;cooling&#x20;water&#x20;for&#x20;the&#x20;use&#x20;of&#x20;intermediate&#x20;and&#x20;high&#x20;pressure&#x20;subcoolers&#x20;helped&#x20;increase&#x20;the&#x20;COP&#x20;further.&#x20;When&#x20;the&#x20;individual&#x20;cooling&#x20;water&#x20;for&#x20;the&#x20;intermediate&#x20;and&#x20;high&#x20;pressure&#x20;subcoolers&#x20;was&#x20;roughly&#x20;10%&#x20;of&#x20;the&#x20;total&#x20;condenser&#x20;cooling&#x20;water,&#x20;the&#x20;optimum&#x20;COP&#x20;was&#x20;achieved&#x20;showing&#x20;an&#x20;additional&#x20;11%&#x20;increase&#x20;in&#x20;COP&#x20;as&#x20;compared&#x20;to&#x20;that&#x20;of&#x20;the&#x20;&amp;apos;non-split&#x20;type&amp;apos;&#x20;for&#x20;the&#x20;three-stage&#x20;heat&#x20;pump&#x20;system.&#x20;(C)&#x20;2000&#x20;Elsevier&#x20;Science&#x20;Ltd&#x20;and&#x20;IIR.&#x20;All&#x20;rights&#x20;reserved.</dcvalue>
<dcvalue element="language" qualifier="none">English</dcvalue>
<dcvalue element="publisher" qualifier="none">ELSEVIER&#x20;SCI&#x20;LTD</dcvalue>
<dcvalue element="title" qualifier="none">A&#x20;study&#x20;on&#x20;the&#x20;performance&#x20;of&#x20;multi-stage&#x20;condensation&#x20;heat&#x20;pumps</dcvalue>
<dcvalue element="type" qualifier="none">Article</dcvalue>
<dcvalue element="identifier" qualifier="doi">10.1016&#x2F;S0140-7007(99)00083-3</dcvalue>
<dcvalue element="description" qualifier="journalClass">1</dcvalue>
<dcvalue element="identifier" qualifier="bibliographicCitation">INTERNATIONAL&#x20;JOURNAL&#x20;OF&#x20;REFRIGERATION-REVUE&#x20;INTERNATIONALE&#x20;DU&#x20;FROID,&#x20;v.23,&#x20;no.7,&#x20;pp.528&#x20;-&#x20;539</dcvalue>
<dcvalue element="citation" qualifier="title">INTERNATIONAL&#x20;JOURNAL&#x20;OF&#x20;REFRIGERATION-REVUE&#x20;INTERNATIONALE&#x20;DU&#x20;FROID</dcvalue>
<dcvalue element="citation" qualifier="volume">23</dcvalue>
<dcvalue element="citation" qualifier="number">7</dcvalue>
<dcvalue element="citation" qualifier="startPage">528</dcvalue>
<dcvalue element="citation" qualifier="endPage">539</dcvalue>
<dcvalue element="description" qualifier="journalRegisteredClass">scie</dcvalue>
<dcvalue element="description" qualifier="journalRegisteredClass">scopus</dcvalue>
<dcvalue element="identifier" qualifier="wosid">000088792400004</dcvalue>
<dcvalue element="identifier" qualifier="scopusid">2-s2.0-0034325804</dcvalue>
<dcvalue element="relation" qualifier="journalWebOfScienceCategory">Thermodynamics</dcvalue>
<dcvalue element="relation" qualifier="journalWebOfScienceCategory">Engineering,&#x20;Mechanical</dcvalue>
<dcvalue element="relation" qualifier="journalResearchArea">Thermodynamics</dcvalue>
<dcvalue element="relation" qualifier="journalResearchArea">Engineering</dcvalue>
<dcvalue element="type" qualifier="docType">Article</dcvalue>
<dcvalue element="subject" qualifier="keywordAuthor">heat&#x20;pump</dcvalue>
<dcvalue element="subject" qualifier="keywordAuthor">refrigerating&#x20;cycle</dcvalue>
<dcvalue element="subject" qualifier="keywordAuthor">multistage&#x20;system</dcvalue>
<dcvalue element="subject" qualifier="keywordAuthor">performance</dcvalue>
<dcvalue element="subject" qualifier="keywordAuthor">calculation</dcvalue>