부동액 도포에 의한 핀-튜브 열교환기 착상방지
- Other Titles
- Frost Prevention of Fin-Tube Heat Exchanger by Spreading Antifreezing Solution
- Authors
- 오상엽; 장영수
- Issue Date
- 2006-06
- Publisher
- 대한설비공학회
- Citation
- 설비공학 논문집, v.18, no.6, pp.477 - 485
- Abstract
- A study on frost prevention of fin-tube heat exchanger is experimently performed by spreading antifreezing solution on heat exchanger surface. It is desirable that the antifreezing solution spreads completely on the surface forming thin liquid film to prevent frost nucleation and crystal growth and to reduce the thermal resistance across the liquid film. A small amount of antifreezing solution falls in drops on heat exchanger surface using two types of supplying devices, and a porous layer coating technique is adopted to enhance the wettedness of antifreezing solution on the surface. It is observed that the antifreezing solution liquid film prevents fin-tube heat exchanger from frosting, and heat transfer performance does not degrade through the frosting tests. The concentration of supplied antifreezing solution can be determined by heat transfer analysis of the first row of heat exchanger to avoid antifreezing solution freezing due to dilution by moisture absorption.
- Keywords
- Antifreezing solution(부동액); Frost prevention(착상방지); Fin-Tube heat exchager (핀-튜브 열교환기); Micro liquid film(마이크로 액막)
- ISSN
- 1229-6422
- URI
- https://pubs.kist.re.kr/handle/201004/135448
- Appears in Collections:
- KIST Article > 2006
- Files in This Item:
There are no files associated with this item.
- Export
- RIS (EndNote)
- XLS (Excel)
- XML
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.