재생증발식 수냉각기의 냉각성능 해석

Other Titles
Investigation on the Cooling Characteristics of a Regenerative Evaporation Water Cooler
Authors
최봉수홍희기이대영
Issue Date
2006-05
Publisher
대한설비공학회
Citation
설비공학 논문집, v.18, no.5, pp.393 - 401
Abstract
The regenerative evaporation water cooler is devised and analysed in this study. The regenerative evaporation water cooler is composed of a sensible heat exchanger to cool the incoming air, followed by a latent heat exchanger to cool the water evaporatively with the cooled air flowing out of the sensible heat exchanger. By linearizing psychrometric characteristics, the heat and mass transfer in the regenerative evaporation water cooler is analyzed theoretically. The results show that the water can be cooled down even lower than the wet-bulb temperature of the inlet air. When the inlet air is 32℃ and 20% in relative humidity, and the inlet temperature of the water is 20℃, the regenerative evaporation water cooler provides a larger cooling capacity than the conventional evaporation water cooler if the effectiveness of the latent heat exchanger is higher than 0.6 and that of the sensible heat exchanger is higher than 0.5.
Keywords
Regenerative evaporation water cooler(재생증발식 수냉각기); Ntu(전달 단위수); Effectiveness(유용도); Cooling capacity(냉각용량)
ISSN
1229-6422
URI
https://pubs.kist.re.kr/handle/201004/135533
Appears in Collections:
KIST Article > 2006
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML

qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.