액체식 직접 접촉 냉각장치의 노즐배열 최적화:정풍량 해석

Other Titles
Optimization of Nozzle Arrangement in a Liquid Direct Contact Cooling System:Constant InletFlowrate Analysis
Authors
김원년김서영
Issue Date
2006-05
Publisher
대한설비공학회
Citation
설비공학 논문집, v.18, no.5, pp.402 - 409
Abstract
For the design of a liquid direct contact cooling system, thermal and hydraulic analysis has been carried out. Well-known Zukauskas correlations are used to estimate the Nusselt number between the liquid refrigerant columns and the inlet airflow. The inlet air velocity is set at a typical value used in an actual showcase. For a constant column number, the best nozzle arrangement is determined for the maximum heat transfer. Heat transfer increases as the transverse pitch of the refrigerant column decreases. Among all the cases dealt with in the present study, the staggered arrangement with 140-columns of 14×10 shows the best thermal performance and the expected temperature drop is 27.8℃. The effect of downstream refrigerant columns on the overall thermal performance is investigated as well.
Keywords
Showcase(쇼케이스); Zukauskas correlation(주카우스카스 상관식); Liquid direct contact cooling(액체식 직접 접촉 냉각)
ISSN
1229-6422
URI
https://pubs.kist.re.kr/handle/201004/135536