CO2 이용 열펌프의 실외열교환기 성능에 관한 실험적 연구

Other Titles
An Experimental Study on the Performance of Outdoor Heat Exchanger for Heat Pump Using CO2
Authors
장영수이민규안영산김영일
Issue Date
2005-02
Publisher
대한설비공학회
Citation
설비공학 논문집, v.17, no.2, pp.101 - 109
Abstract
The purpose of this study is to investigate the performance of outdoor heat exchanger for heat pump using carbon dioxide. Two types of fin and tube heat exchangers (2 rows for type A and 3 rows for B) are tested. Both heat exchangers have counter-cross flow and 1-circuit arrangement. Test results such as heat transfer rate, pressure drop characteristics and temperature distribution in the heat exchanger are shown with respect to mass flow rate of refrigerant and frontal air velocity. For cooling mode, the minimum temperature difference between air and refrigerant of type B is smaller than that of type A by 1 , but the pressure loss of air side is much higher for type B by 29%. It is found that a large temperature gradient of carbon dioxide during gas cooling process promotes thermal conduction through tube wall and fins which results in degradation of heat transfer performance. For heating mode operation, type B heat exchanger shows higher heat transfer performance compared to type A. However, because pressure loss of refrigerant side of type B is much greater than that of type A, the refrigerant outlet pressure of type B becomes lower than that of type A.
Keywords
Heat pump; Carbon dioxide; Outdoor heat exchanger; Gas cooling; Evaporation; 열펌프; 이산화탄소; 실외열교환기; 증발
ISSN
1229-6422
URI
https://pubs.kist.re.kr/handle/201004/136779
Appears in Collections:
KIST Article > 2005
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML

qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE