제습기 성능분석을 위한 선형화 모델 및 해석해의 검증

Other Titles
Development of a Linearized Model and Verification of the Exact Solution for the Analysis of a Desiccant Dehumidifier
Authors
이길봉이대영김민수
Issue Date
2004-09
Publisher
대한설비공학회
Citation
설비공학 논문집, v.16, no.9, pp.811 - 819
Abstract
A silica gel desiccant dehumidifier is studied theoretically in this paper adopting several linearization assumptions. The governing equations are linearized with the assumptions, and the exact solutions to the temperature and the humidity ratio are obtained. In spite of the assumptions, the theoretical results are found to agree well with those from the numerical analysis without any assumption. In typical operation ranges of the desiccant dehumidifier, the time-averaged errors in the process air temperature and humidity ratio are less than 4% and 7%, respectively, and the corresponding root-mean-square values are less than 5% and 15%, respectively. The analytical solutions are expected to contribute to the fundamental understanding of the dehumidification and regeneration processes and the correlation analysis of the numerous parameters influencing the dehumidifier operation.
Keywords
제습제; 제습기; 선형화; 오차; Desiccant; Dehumidifier; Linearization; Error; Desiccant; Dehumidifier; Linearization; Error