베이즈 분류기를 이용한 수냉식 냉동기의 고장 진단 방법에 관한 실험적 연구

Other Titles
An Experimental Study on Fault Detection and Diagnosis Method for a Water Chiller Using Bayes Classifier
Authors
이흥주장영수강병하
Issue Date
2008-07
Publisher
대한설비공학회
Citation
설비공학 논문집, v.20, no.7, pp.508 - 516
Abstract
Fault detection and diagnosis(FDD) system is beneficial in equipment management by providing the operator with tools which can help find out a failure of the system. An experimental study has been performed on fault detection and diagnosis method for a water chiller. Bayes classifier, which is one of classical pattern classifiers, is adopted in deciding whether fault occurred or not. Failure modes in this study include refrigerant leakage, decrease in mass flow rate of the chilled water and cooling water, and sensor error of the cooling water inlet temperature. It is possible to detect and diagnose faults in this study by adopting FDD algorithm using only four parameters(compressor outlet temperature, chilled water inlet temperature, cooling water outlet temperature and compressor power consumption). Refrigerant leakage failure is detected at 20% of refrigerant leakage. When mass flow rate of the chilled and cooling water decrease more than 8% or 12%, FDD algorithm can detect the faults. The deviation of temperature sensor over 0.6℃ can be detected as fault.
Keywords
고장검출; 고장진단; 수냉식 냉동기; 베이즈 분류기; Fault detection; Fault diagnosis; Water chiller; Bayes classifier
ISSN
1229-6422
URI
https://pubs.kist.re.kr/handle/201004/133333
Appears in Collections:
KIST Article > 2008
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML

qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE