Full metadata record

DC Field Value Language
dc.contributor.author김영일-
dc.contributor.author김성실-
dc.date.accessioned2024-01-21T06:13:26Z-
dc.date.available2024-01-21T06:13:26Z-
dc.date.created2021-09-06-
dc.date.issued2004-10-
dc.identifier.issn1229-6422-
dc.identifier.urihttps://pubs.kist.re.kr/handle/201004/137188-
dc.description.abstractIn this study, measurement and analysis of energy consumption of a research building have been conducted. The energy audit procedure includes monitoring of electricity and LNG consumption over a period of three years from 2000 to 2002. Data acquisition system for collecting energy consumption data of HVAC equipment such as chillers, fan filter units, AHUs, cooling towers, boilers, pumps, fan coil units, air compressors and etc. has been installed in a building located in Seoul. Data collected at an interval of 1 minute are analyzed for studying the energy consumption pattern of a research building. Percentage of energy consumption of all HVAC equipment is 51.0% in 2000, 55.4% in 2001, and 62.3% in 2002, respectively. Electricity consumption of chillers accounts for 17.6% of the total energy consumption, which is the largest. Annual energy consumption-rate per unit area is 840.5 Mcal/m2.y in 2000, 1,064.8 Mcal/m2.y in 2001, and 1,393.0 Mcal/m2.y year 2002, respectively.-
dc.publisher대한설비공학회-
dc.title연구용 건물의 열원 및 공조기기의 에너지 소비량 측정 및 분석-
dc.title.alternativeMeasurement and Analysis of Energy Consumption of HVAC Equipment of a Research Building-
dc.typeArticle-
dc.description.journalClass2-
dc.identifier.bibliographicCitation설비공학 논문집, v.16, no.10, pp.914 - 922-
dc.citation.title설비공학 논문집-
dc.citation.volume16-
dc.citation.number10-
dc.citation.startPage914-
dc.citation.endPage922-
dc.description.journalRegisteredClasskci-
dc.identifier.kciidART001101716-
dc.subject.keywordAuthor측정-
dc.subject.keywordAuthor에너지 소비량-
dc.subject.keywordAuthor에너지 원단위-
dc.subject.keywordAuthor에너지 진단-
dc.subject.keywordAuthorHVAC 시스템-
dc.subject.keywordAuthor연구용 빌딩-
dc.subject.keywordAuthorMeasurement-
dc.subject.keywordAuthorEnergy consumption-
dc.subject.keywordAuthorEnergy consumption-rate-
dc.subject.keywordAuthorEnergy diagnosis-
dc.subject.keywordAuthorHVAC system-
dc.subject.keywordAuthorResearch building-
dc.subject.keywordAuthorMeasurement-
dc.subject.keywordAuthorEnergy consumption-
dc.subject.keywordAuthorEnergy consumption-rate-
dc.subject.keywordAuthorEnergy diagnosis-
dc.subject.keywordAuthorHVAC system-
dc.subject.keywordAuthorResearch building-