이산화탄소용 핀-관 증발기의 성능해석
- Other Titles
- Performance Analysis of Fin-tube Evaporator for Carbon Dioxide
- Authors
- 김영일; 이민규; 장영수; 김용찬
- Issue Date
- 2004-07
- Publisher
- 대한설비공학회
- Citation
- 설비공학 논문집, v.16, no.7, pp.645 - 651
- Abstract
- Fin-tube evaporator for carbon dioxide has been investigated both by experiment and simulation. Inside refrigerant heat transfer and outside heat and mass transfer of a wet surface heat exchanger were modeled using appropriate correlations. The results estimated by the calculation were in good agreement with the experimental results. The simulation errors were less than 7.9% for estimating capacity, 0.6℃ for air exit temperature, 1.2% for air exit humidity and 17% for CO2 exit pressure. The simulation program was used to study the effect of air flow direction, number of rows and refrigerant circuits. For a 2-row evaporator, parallel flow showed better performance for low air velocity but for high air velocity, counterflow was better. Refrigerant circuits, however, showed insignificant effect on the performance.
- Keywords
- 증발기; 이산화탄소; 열전달; 핀-관; 실험; 모사; Evaporator; Carbon dioxide; Heat transfer; Fin-tube; Experiment; Simulation
- ISSN
- 1229-6422
- URI
- https://pubs.kist.re.kr/handle/201004/137443
- Appears in Collections:
- KIST Article > 2004
- Files in This Item:
There are no files associated with this item.
- Export
- RIS (EndNote)
- XLS (Excel)
- XML
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.