dc.description.abstractGalvanized Steel pipes have been widely used in industries and apartments. Unexpected early leakage has been found in an apartment. Tunneling corrosion or penetration was found in the water supply pipes. The chemical compositions of the pipes and properties of coating layer were evaluated. The pipes met the specification of KS D 3507. The cause of early failure was analyzed through the examination of macrostructures and microstructures. It was found that the pipes were failed by grooving corrosion, which resulted from galvanic corrosion of weld bead and matrix.-
dc.publisher한국부식방식학회-
dc.titleFailure Analysis of Welded Pipe in Water Supplies for Apartment-
dc.typeArticle-
dc.description.journalClass2-
dc.identifier.bibliographicCitationCORROSION SCIENCE AND TECHNOLOGY, v.3, no.2, pp.67 - 71-
dc.citation.titleCORROSION SCIENCE AND TECHNOLOGY-
dc.citation.volume3-
dc.citation.number2-
dc.citation.startPage67-
dc.citation.endPage71-
dc.description.journalRegisteredClasskci-
dc.description.journalRegisteredClassother-
dc.identifier.kciidART000949331-
dc.subject.keywordAuthorgrooving corrosion-
dc.subject.keywordAuthorgalvanized steel pipes-
dc.subject.keywordAuthorelectrical resistance welding(ERW)-
dc.subject.keywordAuthormetal flow-
dc.subject.keywordAuthorbond zone-