Modeling and performance simulation of a gas cooler for a CO2 heat pump system

Authors
Chang, Young-SooKim, Min Seok
Issue Date
2007-05
Publisher
TAYLOR & FRANCIS INC
Citation
HVAC&R RESEARCH, v.13, no.3, pp.445 - 456
Abstract
The outlet temperature of a gas cooler has a great effect on the efficiency of carbon dioxide heat pump systems. In order to obtain a small approach temperature difference at the gas cooler, a near-counterflow type heat exchanger has been proposed, and a larger heat transfer area is demanded. Therefore, the optimum design for gas coolers involving the analysis of trade-offs between heat transfer performance and cost is desirable. For this study, a simulation model has been developed for fin-and-tube type gas coolers, and an air-side heat transfer correlation is proposed. The developed model was confirmed by experimental results. The effects of geometric parameters, such as transverse tube spacing, longitudinal tube spacing, number of tube rows, and fin spacing, on the performance of heat exchangers were investigated using the developed model. This study suggests various simulation results for optimum design of gas coolers.
Keywords
CO2; gascooler; heat pump
ISSN
1078-9669
URI
https://pubs.kist.re.kr/handle/201004/134431
DOI
10.1080/10789669.2007.10390964
Appears in Collections:
KIST Article > 2007
Files in This Item:
There are no files associated with this item.