Effect of desiccant isotherm on the performance of desiccant wheel

Authors
Chung, Jae DongLee, Dae-Young
Issue Date
2009-06
Publisher
ELSEVIER SCI LTD
Citation
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, v.32, no.4, pp.720 - 726
Abstract
Numerical simulation has been conducted for the desiccant wheel, which is the crucial component of a desiccant cooling system. As the key operating/design parameters, the rotation speed and the area ratio of regeneration to dehumidification have been examined for a range of regeneration temperature from 50 degrees C to 150 degrees C. Optimization of these parameters is conducted based on the wheel performance evaluated by means of Moisture Removal Capacity (MRC). Simulations are focused on the effect of desiccant isotherm on the optimal conditions of these operating/design parameters. Also the effects of the outdoor air temperature and humidity on the optimum design parameters are examined. (C) 2009 Elsevier Ltd and IIR. All rights reserved.
Keywords
MASS-TRANSFER; DEHUMIDIFICATION; HEAT; SIMULATION; MASS-TRANSFER; DEHUMIDIFICATION; HEAT; SIMULATION; Air conditioning; Modelling; Desiccant wheel; Simulation; Mass transfer; Optimization; Variable speed
ISSN
0140-7007
URI
https://pubs.kist.re.kr/handle/201004/132433
DOI
10.1016/j.ijrefrig.2009.01.003
Appears in Collections:
KIST Article > 2009
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML

qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.