In-situ performance test and simulation of an air source heat pump

Authors
Baik, YJChang, YSKim, Y
Issue Date
2000-11
Publisher
JAPAN SOC MECHANICAL ENGINEERS
Citation
JSME INTERNATIONAL JOURNAL SERIES B-FLUIDS AND THERMAL ENGINEERING, v.43, no.4, pp.628 - 633
Abstract
In this study, in-situ performance test of a 20 RT (70 kW) air-to-air heat pump which has a feature of recovering ventilation energy is carried out. Since test conditions such as indoor and outdoor air conditions cannot be controlled to satisfy the standard test conditions, experiments are done with the inlet air conditions as they exist. From the experimental data obtained with the non-standard test conditions, simulation program is developed to estimate the performance of standard test conditions. The map-based compressor model, epsilon -NTU method with the assumption of refrigerant-side mixed and air-side unmixed and necessary parameters determined from the measurements are used. From the simulation, performance of a large capacity air source heat pump for various conditions and effects of ventilation are calculated. This study provides method of predicting the performance of air source heat pumps in which in-situ performance test is necessary.
Keywords
FLOW; FLOW; air source; heat pump; in-situ performance test; simulation; ventilation energy recovery; map-based compressor model; heat exchanger; epsilon-NTU
ISSN
1340-8054
URI
https://pubs.kist.re.kr/handle/201004/140975
Appears in Collections:
KIST Article > 2000
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML

qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE